Integrator Windup and How to Avoid It¶
Astrom, K. J., & Rundqwist, L. (1989). Integrator Windup and How to Avoid It. 1989 American Control Conference, 1693-1698.
Cited by¶
1 citation across 1 artifact.
Each citation links to the sentence it supports in the citing article.
Mechanisms¶
- Process Control Tuning
- Its classic failure is integral windup: when the actuator saturates, the integral term keeps accumulating error it can't act on, so when the state finally moves the controller overcorrects violently and the system lurches or oscillates.
This sourceExplains integrator windup under actuator saturation, including accumulated integral action, large overshoot, and oscillatory recovery.
- Its classic failure is integral windup: when the actuator saturates, the integral term keeps accumulating error it can't act on, so when the state finally moves the controller overcorrects violently and the system lurches or oscillates.
Verification¶
This reference passed the adversarial substantiation pipeline: it was checked to exist and to support the claim it is attached to. See how references were verified.
Registry ID ref:f78fc2d09b20 · see in the full table